International Journal of Science and Research (IJSR)

International Journal of Science and Research (IJSR)
Call for Papers | Fully Refereed | Open Access | Double Blind Peer Reviewed

ISSN: 2319-7064


Downloads: 148 | Views: 211 | Weekly Hits: ⮙1 | Monthly Hits: ⮙1

Research Paper | Medicine Science | India | Volume 6 Issue 5, May 2017


Seasonal Performance Study of Solar Cooling System under Indian Climatic Conditions

A. Mahesh [3]


Abstract: This paper provides performance analysis of an adsorption refrigeration system under three seasons viz. , winter, monsoon and summer. The present system is studied in terms of the solar coefficients of performance (COPsolar). An average radiation was obtained 512 W/m2 in winter, 602 W/m2 in monsoon and 846 W/m2 in summer season. The yearly mean ambient temperature was recorded in the range of 25.639.5C. Desorption temperature varied from 80-83C, 83-110C and 80-117C for the respective seasons. The test results show that COPsolar varied for winter, monsoon and summer seasons as 0.55, 0.59 and 0.71, respectively. It is found out that radiation under which 700-850W/m2 the adsorption refrigeration system was given better performance for Indian climatic conditions.


Keywords: Solar refrigeration, Seasonal performance, Year round analysis, Solar coefficient of performance


Edition: Volume 6 Issue 5, May 2017,


Pages: 433 - 438


How to Download this Article?

Type Your Valid Email Address below to Receive the Article PDF Link


Verification Code will appear in 2 Seconds ... Wait

Top