International Journal of Science and Research (IJSR)

International Journal of Science and Research (IJSR)
Call for Papers | Fully Refereed | Open Access | Double Blind Peer Reviewed

ISSN: 2319-7064


Downloads: 116

Research Paper | Electrical Engineering | Ghana | Volume 5 Issue 6, June 2016


Load Assessment/Evaluation of a Three Phase Four Wire Distribution System of a Technical Institution. A Case Study of Kumasi Polytechnic, Ghana.

Kwadwo Ntiamoah-Sarpong [4] | Kwame Sarfo | Johannex Fefeh. Rushman | Achiaa Donkor


Abstract: A power system is subjected to numerous interruptions such as stresses, extension, and aging of system components, which degrade the power system and add harmonic properties to the system which eventually compromise the reliability and stability of the power system. The degradation is primarily of unmonitored changes which have been added to the system. Evaluation of these changes in the system helps in resolving load imbalances which lead to high current unbalances. High current unbalance is a measure of the health of a wye distribution system. Electric load monitoring generates important data that can help to unravel the mystery behind premise usage characteristics in commercial and industrial facilities. The high unbalanced phases in the institution distribution system, has resulted in high values of neutral currents in the system. The average value of neutral current within each cluster is very high. Increase in neutral currents leads to increase in I2R losses, and a decrease in the transformer efficiency. Unbalanced phases can lead intermittent failure of breakers and to fire outbreaks. . Percentage current Unbalance in each cluster has highly exceeded 10 % of acceptable limit. Some loads need to be powered from appropriate phase to ensure balancing.


Keywords: Load assessment, phase current, current unbalance, efficiency, health status


Edition: Volume 5 Issue 6, June 2016,


Pages: 147 - 153


How to Download this Article?

You Need to Register Your Email Address Before You Can Download the Article PDF


How to Cite this Article?

Kwadwo Ntiamoah-Sarpong, Kwame Sarfo, Johannex Fefeh. Rushman, Achiaa Donkor, "Load Assessment/Evaluation of a Three Phase Four Wire Distribution System of a Technical Institution. A Case Study of Kumasi Polytechnic, Ghana.", International Journal of Science and Research (IJSR), Volume 5 Issue 6, June 2016, pp. 147-153, https://www.ijsr.net/get_abstract.php?paper_id=NOV163903

Similar Articles with Keyword 'phase current'

Downloads: 109

Research Paper, Electrical Engineering, India, Volume 9 Issue 7, July 2020

Pages: 1926 - 1930

Induction Motor Parameter Monitoring System using Zig bee Protocol & MATLAB GUI: Automated Monitoring System

Sachin Mali | Sunil Kumar Bhatt

Share this Article

Downloads: 118

M.Tech / M.E / PhD Thesis, Electrical Engineering, India, Volume 8 Issue 8, August 2019

Pages: 826 - 831

Variance Index of DWT Based Symmetrical Fault during Power Swing

Eswararao Bireddi | Kumarraja.A [4] | E. Suresh

Share this Article
Top